Help for MP App
V1.0
English
The MP App is a simple utility for configuring the input/output module MP24-AIO. This document describes the features of the application, see also MP24-AIO manual for detailed information about the device itself. The purpose of the utility is to change device settings and manage firmware updates.
Device info
· Serial number
· Firmware version
· Hardware version
Analog outputs
· Actual output voltage (the range is 0…10 V)
· Output value editor
Analog inputs
· MP address (PP, MP1 … MP8)
· Actual input value (interpretation is based on value type)
· Input value type (see the table below)
· MP Address setting
· Value type setting
The changes to analog outputs and inputs must be confirmed by APPLY button or the Enter key.
Analog input types |
||||
|
Label |
Meaning |
Value range |
Integer encoding |
0 |
None |
Turned off |
0 |
0 |
1 |
VOLTAGE |
Voltage |
0 to 10 V |
0…10000 |
2 |
RESISTOR1 |
Resistance – range 1 |
100 Ω to 5 kΩ |
100…5000 |
3 |
RESISTOR2 |
Resistance – range 2 |
100 Ω to 60 kΩ |
100…60000 |
4 |
Switch |
Switch state |
1 (0–2 V); 0 (> 2 V) |
0…1 |
5 |
CURRENT |
Electrical current |
0 to 20 mA |
0…2000 |
6 |
PT1000 |
Temperature sensor Pt 1000 |
-40,0 to 220 °C |
-400…2200 |
7 |
NI1000_5000 |
Temperature sensor Ni 1000 (Tk 5000) |
-40,0 to 220 °C |
-400…2200 |
8 |
NI1000_6180 |
Temperature sensor Ni 1000 (Tk 6180) |
-40,0 to 220 °C |
-400…2200 |
|
|
|
|
|
The connection is via USB interface. The device implements Virtual COM Port (VCP) interface, it appears as a serial port. The device driver should be installed automatically when the device is first connected. The Windows operating system assigns a unique COM port during the installation. If more than one device is used on a single computer, each device has a different port number assigned. The assigned COM port can be changed in Device Manager.
1. Connect the device using USB to your computer
2. Wait for driver installation
3. Start the application
4. Select the correct serial port
5. Click Connect
Note: If there are many COM ports available on the computer, the following procedure can be used to determine the right one:
1. Connect the device to the computer (or disconnect if it has been already connected)
2. Update the list of available ports
3. Check out what port appears in the list (or disappears)
The actual firmware is available for download at FIRVENA website (https://www.firvena.com/en/input-output-module-with-mp-bus-communication/p-28/).
1. Download the firmware file
2. Connect the device
3. Open the firmware file (dragging the file into the Firmware update box also works)
4. Use Upload button to write the file into the device
5. Use Restart button to reboot the device
6. Disconnect the USB cable for a while
Now the device performs reprogramming, wait until the green PWR LED shines again.
7. Start communication
8. Check the firmware version
Date |
Version |
Description |
2023-07-26 |
V1.0 |